HIGH PRESSURE CUTOUT (HPCO) CONTROL
Water Cooled Only
FUNCTION
Stops the ice machine if subjected to excessive high-
side pressure.
The HPCO control is normally closed, and opens on a
rise in discharge pressure.
SPECIFICATIONS
Cut-out: 20.7 Bar (300 psig)
Cut-in: 10.3 Bar (150 psig)
(Must be below ± .7 Bar, ± 10 psig to reset).
CHECK PROCEDURE
1. Set ON/OFF/WASH switch to OFF.
2. Connect manifold gauges.
3. Hook voltmeter in parallel across the HPCO,
leaving wires attached.
4. Close the valve to the water condenser inlet.
5. Set ON/OFF/WASH switch to ON.
6. No water flowing through the condenser will cause
the HPCO control to open because of excessive
pressure. Watch the pressure gauge and record the
cut-out pressure.
Replace the HPCO control if it:
Will not reset (below 10.3 Bar [150 psig])
Does not open at the specified cut-out point
!
Warning
If discharge pressure exceeds 21.4 Bar (310 psig)
and the HPCO control does not cut out, set ON/
OFF/WASH switch to OFF to stop ice machine
operation.
Summary of Contents for EC18
Page 2: ......
Page 6: ...This Page Intentionally Left Blank ...
Page 12: ...This Page Intentionally Left Blank ...
Page 14: ... 2 This Page Intentionally Left Blank ...
Page 24: ...12 Part Number 80 1479 3 10 10 Evaporator Ice Chute Spray Bar Spray Nozzles Toggle Switch ...
Page 42: ...30 Part Number 80 1479 3 10 10 This Page Intentionally Left Blank ...
Page 74: ...62 Part Number 80 1479 3 10 10 This Page Intentionally Left Blank ...
Page 75: ...Part Number 80 1479 3 10 10 63 ...
Page 100: ... 87 This Page Intentionally Left Blank ...
Page 101: ... 88 This Page Intentionally Left Blank ...
Page 175: ... 162 This Page Intentionally Left Blank ...
Page 181: ... 168 ...
Page 182: ......
Page 183: ......