7. 70Ø 1 metre extensions (including support bracket), and additional 93° & 45° elbows are available. Any additional 93° & 45° elbows must be
accounted for when calculating flue lengths. 70Ø 93° elbows are equivalent to 3.5 metres of straight length and 45° elbows to 1 metre.
NOTE
: Permitted positions of the plume outlet relative to doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation & Servicing Instructions and BS5440 Pt. 1.
It is
NOT
necessary to fit a terminal guard over the air inlet or the plume outlet.
Fig. A & Fig. B