NOTE
: Horizontal flue pipes should always be installed with a 1.5° fall from the
terminal to allow condensate to run back to the boiler.
page 22
8.2 Twin & Vertical Flue Systems
Concentric
The maximum equivalent lengths are 4m
(vertical). Their lengths exclude the standard elbow and terminal assembly (vertical).
Twin Flue
The total maximum equivalent flue length is 150m
.
NOTE
: Each 1m of flue duct should be calculated as 2m.
Any additional "in line"
bends in the flue system must be taken into consideration. Their equivalent lengths are: