Maguire Products, Inc.
Rev. December 18, 2019
– ULTRA-1000 Touchscreen
51
ULTRA By Maguire
- Ultra Low Energy Dryer
RMP - Temperature Ramp Settings
format:
xyyzz (increments / minutes / °F or °C)
function(s):
x:
Number of temperature steps during a temperature ramp.
yy:
Duration of a temperature ramp.
zz:
Temperature span of a temperature ramp.
CTM - Cooldown Temperature
format:
xxxxx (°F or °C)
function(s):
Heating hopper cooldown temperature target.
Note: Cooldown mode must be enabled for this parameter to have effect.
CTR - Cooldown Timer
format:
xxxxx (minutes)
function(s):
Heating hopper cooldown time.
Note: Cooldown mode must be enabled for this parameter to have effect.
H1W - Heating Hopper Heater Wattage
format:
xxxxx (Watts)
function(s):
Wattage of the primary heater. This value is used in energy consumption calculations.
PGS - Purge Heater Setpoint
[ULTRA-600 and ULTRA-1000 only]
format:
xxxxx (°F or °C)
function(s):
Purge / blanketing air setpoint temperature.
PT2 - Purge Heater Proportional Term
[ULTRA-600 and ULTRA-1000 only]
format:
xxxxx (constant)
function(s):
Purge heater PID control loop proportional term. This term makes adjustments to the
purge heater output that are directly proportional to the current error.