Maguire Products, Inc.
Rev. December 18, 2019
– ULTRA-1000 Touchscreen
48
ULTRA By Maguire
- Ultra Low Energy Dryer
Heater
PTS - Preheat Temperature Setpoint
format:
xxxxx (°F or °C)
function(s):
Target heating hopper air inlet temperature during preheat (when the Preheat Setpoint is
set to
“Temperature”).
PHT - Preheat Time
format:
xxxxx (minutes)
function(s):
1. When Preheat mode is set to “Auto”, this is the
minimum
preheat duration.
2. When Preheat mode is set to “Timed”, this is the preheat duration.
PHD - Preheat Differential Temperature
format:
xxxxx (°F or °C)
function(s):
When Preheat Setpoint mode is set to “Differential”, the preheat temperature is
automatically set to this number of degrees below the run temperature (RTS).
PTD - Preheat Target Delta
format:
xxxxx (°F or °C)
function(s):
When Preheat mode is set to “Auto”, the preheat will automatically terminate when the
heating hopper exit air temperature is within this number of degrees of the preheat
temperature, assuming PHT has expired.
RTS - Run Temperature Setting
format:
xxxxx (°F or °C)
function(s):
Target heating hopper air inlet temperature during preheat (when Preheat Setpoint is set
to “Same as Run Temp.”) and during all subsequent heating cycles.
PT1 - Heating Hopper Heater Proportional Term
format:
xxxxx (constant)
function(s):
Heating hopper heater PID control loop proportional term. This term makes adjustments
to the heater output that are directly proportional to the current error.