AC Input Fusing Selection
159
AC Input Fusing Selection
North America
Rated
Input
Voltage
Rated
HP
Rated
kW
Model
Number
Cube
size
Fuse Size (in Amps)
10
7.5
-4018
B
25 to 45 A
15
11
-4024
B
35 to 45 A
20
15
-4034
C
45 to 100 A
380V
to
480V
25
18
-4039
C
50 to 100 A
7.5
5.5
-2028
A
45 to 100 A
10
7.5
-2035
B
60 to 100 A
15
11
-2047
B
80 to 100 A
200V
to
240V
20
15
-2060
C
100 to 200 A
All fuses should be Class J, Low Peak Dual Element, Time delay 600VAC fuses.
European
Rated
Input
Voltage
Rated
kW
Model
Number
Cube
size
Fuse Size (in Amps)
4
-4011
A
16 to 45 A
5.5
-4015
A
25 to 45 A
7.5
-4021
B
25 to 45 A
11
-4028
B
35 to 45 A
380V
to
440V
15
-4039
C
45 to 100 A
All fuses should be Class J, Low Peak Dual Element, Time delay 600VAC fuses.
NOTE: With all models circuit breakers can be substituted for fuses in accordance with local codes