Range: 0, 1
n
n 4
4 3
3
F
FR
R F
Fu
un
nc
cttiio
on
n
Factory Setting: 0
This constant sets the function of control circuit terminal FR.
Setting
Function
0
External frequency reference signal input (0-10 VDC
or 4-20mA) ref terminal FC
1
External fault reset signal input (when shorted to
terminal FS, drive performs fault reset)
C
Co
on
ns
stta
an
ntt A
An
na
allo
og
g M
Mo
on
niitto
orr S
Se
elle
ec
cttiio
on
n Factory Setting: 0
n
n 4
4 4
4
This constant establishes which output parameter will be applied to the Analog
Monitor Output at terminals AM & AC. The Analog Monitor output is a 0-3 VDC
signal, proportional to the output parameter selected.
Setting
Function
0
Output frequency
1
Output current
C
Co
on
ns
stta
an
ntt A
An
na
allo
og
g M
Mo
on
niitto
orr G
Ga
aiin
n
Range: 0.0 - 2.00
n
n 4
4 5
5
Factory Setting: 1.00
This constant calibrates the output signal for the external metering circuit.
At the factory setting, an analog
voltage of approximately 10V is
output when the output frequency
(or output current) is 100%.
Use the following formula to
calculate the proper value
of n
n 4
4 5
5 :
Desired output voltage
n45 setting =
at 100% of Fmax
10V
Example:
For 3V output at 100%,
set n
n 4
4 5
5 to “ 0.30 ”
46
OUTPUT FREQUENCY
(OUTPUT CURRENT)
100%
0
3V
10V
ANALOG OUTPUT