Table 3-1. GPD 205 Constants
Setting Range
Setting
Factory
Ref.
Constant
Name
(and units)
Increment
Setting
Page
Password / Initialization
0, 1, 8, 9
1
1
23
Operation mode selection
0 - 5
1
0
23
Stopping method selection
0, 1
1
0
26
Forward / Reverse run selection
F
or (forward),
— —
F
or
16
rEu (reverse)
Reverse run prohibit selection
0, 1
1
0
26
Multi-function input selection 1
0 - 14
1
1
27
(terminal S1)
Multi-function input selection 2
1 - 14
1
2
(terminal S2)
Multi-function input selection 3
1 - 15
1
4
(terminal S3)
Multi-function output selection 1
0 - 10
1
1
32
(terminals MA & MB)
Multi-function output selection 2
0 - 10
1
0
(terminal PA)
Frequency reference 1
6.0
33
Frequency reference 2
0.1
0.0
Frequency reference 3
(less than
0.0
Frequency reference 4
100 Hz);
0.0
Frequency reference 5
0.0 - 400 (Hz)
1
0.0
Frequency reference 6
(100 Hz or
0.0
Frequency reference 7
more)
0.0
Frequency reference 8
0.0
Jog frequency reference
6.0
35
Acceleration time 1
0.1
10.0
36
(less than
Deceleration time 1
0.0 - 999 (sec)
100 sec)
10.0
Acceleration time 2
1
10.0
(100 sec or
Deceleration time 2
more)
10.0
20