Time chart for Multi-step Speed operation:
Multi-step speed reference 3 is used together with the accel/decel time selection.
When multi-step speed reference 3 is turned OFF, accel/decel time 1 (n
n 2
2 0
0 , n
n 2
2 1
1 ) is
selected. When it is turned ON, accel/decel time 2 (n
n 2
2 2
2 , n
n 2
2 3
3 ) is selected.
C
Co
on
ns
stta
an
ntt
JJo
og
g F
Frre
eq
qu
ue
en
nc
cy
y R
Re
effe
erre
en
nc
ce
e
Factory Setting: 6.0
n
n 1
1 9
9
Range: 0.0 - 400 (Hz)
This constant determines the speed at which the drive will run the motor when the
momentary Jog input (see setting “ 7 ” for multi-function input terminals, on page
27) is applied to the drive. Usually set to a low output frequency level, this setting is
used for jogging the driven machine, an operation primarily used during set-up.
35
(n11) 25.0 Hz
(n12) 30.0 Hz
(n13) 35.0 Hz
(n14) 40.0 Hz
(n15) 45.0 Hz
(n16) 50.0 Hz
(n17) 55.0 Hz
(n18) 60.0 Hz
ON
FWD RUN/STOP
ON
MULTI-STEP
SPEED REF. 1
ON
ON
MULTI-STEP
SPEED REF. 2
MULTI-STEP
SPEED REF. 3
FREQUENCY
TIME
TERMINAL S1
TERMINAL S1
TERMINAL S1
ON
ON
ON
ON
ACCEL/DECEL
TIME SELECT:
ACCEL TIME
DECEL TIME
n20
n22
n20
n21
n23
n21