![background image](http://html1.mh-extra.com/html/magnetek/gpd-205/gpd-205_technical-manual_3603701047.webp)
•
E
Ex
xa
am
mp
plle
es
s o
off V
V/
/ff P
Pa
atttte
errn
n S
Se
ettttiin
ng
g
Set the V/f pattern according to the applications described below. When running at a
frequency exceeding 50/60 Hz, change the maximum output frequency (n
n 2
2 4
4 ).
NOTE: Be sure to set the maximum output frequency according to the motor
characteristics.
1)
General-purpose applications
50 Hz
60 Hz [ Factory Settings ]
2)
Fans/pumps
50 Hz
60 Hz
38
V
f
230
60
1.5
12
V
f
230
50
1.3
12
Constant Setting
n24
50.0
n25
230.0
n26
50.0
n27
1.3
n28
12.0
n29
1.3
n30
12.0
Constant Setting
n24
60.0
n25
230.0
n26
60.0
n27
1.5
n28
12.0
n29
1.5
n30
12.0
V
f
230
60
1.5
10
30
50
V
f
230
50
1.3
10
25
50
Constant Setting
n24
50.0
n25
230.0
n26
50.0
n27
25.0
n28
50.0
n29
1.3
n30
10.0
Constant Setting
n24
60.0
n25
230.0
n26
60.0
n27
30.0
n28
50.0
n29
1.5
n30
10.0
for more: efesotomasyon - Yaskawa drive