![background image](http://html1.mh-extra.com/html/magnetek/gpd-205/gpd-205_technical-manual_3603701031.webp)
Table 3-1. GPD 205 Constants - Continued
Setting Range
Setting
Factory
Ref.
Constant
Name
(and units)
Increment
Setting
Page
DC injection braking current
0 - 100 (%)
1
50
47
DC injection braking time at stop
0.0 - 5.0 (sec)
0.1
0.0
DC injection braking time at start
0.0 - 5.0 (sec)
0.1
0.0
S-curve accel/decel selection
0 - 3
1
0
48
Overtorque detection
0 - 4
1
0
49
Overtorque detection level
30 - 200 (%)
1
160
Overtorque detection time
0 - 9.9 (sec)
0.1
0.1
Frequency detection level
0.0 - 400 (Hz)
0.1
0.0
51
(< 100 Hz);
1
(
≥
100 Hz)
Slip compensation gain
0.0 - 9.9 (%)
0.1
0.0
51
Motor no-load current
0 - 99 (%)
1
40
52
Prohibited frequency 1
0.1
0.0
52
(< 100 Hz);
Prohibited frequency 2
0.0 - 400 (Hz)
1
0.0
(
≥
100 Hz)
Prohibited frequency 3
0.0
Prohibited frequency bandwidth
0.0 - 25.5 (Hz)
0.1
1.0
No. of auto-restart attempts
0 - 10
1
0.0
54
Operator "Stop" key selection
0, 1
1
0
54
Slip compensation delay timer
0.0 - 25.5 (sec)
0.1
2.0
54
Fault record
Stores and displays most recent alarm
54.1
(not user settable).
Cleared by RESET command.
PROM number
Displays last 3 digits of PROM
54.1
number: NSP600300
(not user settable).
NOTES:
1.
Initial value depends upon GPD 205 capacity. See page 17.
2.
Constants n
n 6
6 3
3 thru n
n 6
6 7
7 are reserved for future use.
22
for more: efesotomasyon - Yaskawa drive