Time chart for Accel/Decel Hold Command input:
NOTE: When the FWD (REV) run command is input along with the Accel/Decel Hold
Command, the motor does not operate (holds at zero speed). However, when the
frequency reference lower limit (n
n 4
4 2
2 ) is set greater than or equal to the minimum
output frequency (n
n 2
2 9
9 ), the motor operates at the frequency reference lower limit.
•
L
Lo
oc
ca
all/
/R
Re
em
mo
otte
e s
se
elle
ec
cttiio
on
n ((s
se
ettttiin
ng
g:: ““ 1
14
4 ””))
Selects whether an operation reference is received from the Digital Operator or the
control circuit terminal.
Local/Remote selection is possible only when the drive is stopped.
Open : Run according to the setting of Operation Mode Selection (n
n 0
0 2
2 ).
Closed : Run by frequency reference and run command from the Digital
Operator.
Example: Set n
n 0
0 2
2 to “ 3 ” or “ 5 ”.
Open : Run by frequency reference from control circuit terminal FR and
Run command from control circuit terminals SR and SF.
Closed : Run by frequency reference and Run command from the Digital
Operator.
29
OUTPUT
FREQUENCY
FREQUENCY
REFERENCE
ON
ON
ON
ON
ON
ON
FWD RUN
ACCEL/DECEL
HOLD COMMAND
FREQUENCY
AGREED SIGNAL
TIME