Step 1 

– Installation 

Download the Power Xpert 

in

Control Software with the One Installer found on the

www.eaton.com/dg1

 software tab.

Step 2 

– Connecting 

Keypad Port:

  Using the PowerXL DG1 programming cable (Part Number DXG-

CBL-PCCABLE) connect from your computer USB port to the keypad port.  

Ethernet Port:

 Using any standard CAT5 Ethernet cable connect from your 

computer to the RJ45 Ethernet Port. Note:  Your drive IP address will have to be 
set up in the drive keypad parameters (Group P20.3) to match the IP address 
structure in your computer before connecting. 

Step 3 

– Configuring Connection 

Open Power Xpert 

in

Control and double click on either the Modbus Serial (Keypad Port)

or Modbus TCP (Ethernet Port) on the right side in the 

Device Catalog

 (

red

). Once com-

plete, the device DTM should then show up in the 

Network View 

(

blue

).

If the Modbus Serial (Keypad Port) is selected the 

Communication Settings 

window will

come up which should be set to the following values.

Configuration Parameter 

Setting 

Port 

Need to check in windows device properties for port 
USB to RS485 adapter was installed at. 

Parity* 

Even 

Data Bits* 

Baud Rate* 

38400 

Stop Bits* 

Transmission Mode* 

RTU 