Lucent Technologies Lineage
®
2000 ECS Battery Plant J85500D-3
3 - 22 Engineering, Planning and Ordering
Issue 5 January 1999
Order pre-engineered battery cable kits for use with VR batteries
in supplemental bays can be ordered with the ECS battery plant.
These kits have been engineered for the typical ECS
configurations presented in the J85500D-3 drawing. The kits
contain the following items:
•
Appropriate length and gauge of KS-24194 L2 wire
•
Appropriate lugs for termination at the battery and at the dc
distribution
•
Crimping information
•
Heat shrink tubing
For nontypical ECS configurations where the supplementary
bays are not located adjacent to the initial bay, battery cables
must be engineered to fit the individual installation.
The circuit breakers and fuses available for dc distribution
overcurrent protection are shown in Table 3-H. The breaker or
fuse rating for a given circuit is selected by the criteria covered
above under Overcurrent Protection.
Table 3-G: VR Battery Cable and Lug Information
Cable
Information
Lug Information
Wire Gauge Flex
Class I
WP Spec
Comcode
Die Color
Compression Tools
TBM8 Die
No.
TBM5 Die
No.
TBM6
Upper Die
Lower Die
1/0
WP91412
L57
405348235
black
13462
13455
13474
13477
4/0
WP91412
L27
405347923
yellow
13463
13456
13473
13476
Table 3-H: Field-Installed Components
For List 3 through 6 and 23 through 26 Distribution Panels
Item
Size (Amperes)
Comcode
Description
List 3 through 6 Circuit Breaker Kit Options
1
3
406746313
KS23616 L20
2
5
406746321
KS23616 L21
3
10
406746339
KS23616 L22
4
15
406746347
KS23616 L23
5
20
406746354
KS23616 L24