Lucent Technologies Lineage
®
2000 ECS Battery Plant J85500D-3
7 - 2 Safety
Issue 5 January 1999
manufacturer using only the connector manufacturer's
recommended tooling or tooling approved for that connector.
If the proper connector for the country of installation is not
provided, obtain appropriate connectors and follow
manufacturer's and all local requirements for proper
connections. All national and local rules and regulations are to
be followed when making field connections.
The field wiring connections have been evaluated for connection
of minimum 90°C conductors sized per the U.S. National
Electrical Code using 75°C ampacity tables.
Torque electrical connections to the values specified on labels or
in the product documentation.
Battery input cables must be dressed to avoid damage to the
insulation (caused by routing around sharp edges or routed in
areas where wires could get pinched) and undue stress on the
connectors.
The short circuit current capability of the battery input to the
distribution panel must not exceed 10,000 amperes.
Fuses/circuit breakers may not be provided with the equipment.
Refer to the product documentation for the proper hardware. Use
only the parts specified in the equipment documentation.
Installing fuses or circuit breakers not specified for use in this
equipment may result in injury to service personnel or eqipment
damage.
External loading must not exceed 80% of its fuse/circuit breaker
current rating.
AC branch circuits to this equipment must be protected with
either fuses or circuit breakers sized as required by the National
Electric Code (NEC) and/or local codes. Refer to the equipment
ratings to assure rating of equipment will not exceed 80% of the
value of the protector chosen. Reference drawing T-82670-31
for recommended circuit protection for the different options.
An accessible ac disconnect/protection device to remove ac
power from the equipment in the event of an emergency must be
provided. This device must open all poles and be connected
together.