Lucent Technologies Lineage
®
2000 ECS Battery Plant J85500D-3
Issue 5 January 1999
Safety 7 - 1
7
Safety
Safety
Statements
Please read and follow all safety instructions and warnings
before installing, maintaining, or repairing the power system.
Reference the individual module product manuals for additional
safety statements specific to the modules.
The J85500D-3 ECS Power System is Underwriters laboratories
(UL) Listed per: Subject Letter 1801, DC Power Distribution
Centers for Telecommunications Equipment for use in the USA;
and CSA C22.2 No. 225 for use in Canada. Rectifiers are
individually UL Recognized and/or CSA Certified to UL1950
and CSA C22.2 No. 234/950. Note: J85500D-3 equipped with
List 5 or 6 does not have safety agency Listing.
Install only in restricted access areas (dedicated equipment
rooms, equipment closets, or the like) in accordance with articles
110-16, 110-17, and 110-18 of the U.S. Natinal Electrical Code
(NEC), ANSI/NFPA No. 70, and pursuant to applicable local
codes.
This equipment is to be used in controlled environments (an area
where the humidity is maintained at levels that cannot cause
condensation on the equipment, the contaminating dust is
controlled, and the steady-state ambient temperature is within
the range specified).
This equipment must not be installed over combustible surfaces.
For installations in the U.S. and Canada, Listed/Certified
compression connectors are to be used to terminate Listed/
Certified field-wired conductors where required. For all
installations, the appropriate connector is to be applied only to
the correct size conductor as specified by the connector