Lucent Technologies Lineage
®
2000 ECS Battery Plant J855003D-3
Issue 5 January 1999
Maintenance 5 - 1
5
Maintenance
Controls and
Indicators
Operating controls and indicators on the battery plant are listed
below.
•
Controller LEDs and switches (see Controller Manual)
•
Rectifier LEDs and switches (see Rectifier Manual)
•
LVD/Fuse Board LEDs and fuses
Two LEDs on the LVD/Fuse Board are used to indicate the
status of the low-voltage disconnect/reconnect circuit.
1. The red “LVD OPEN” LED indicates that the disconnect/
reconnect contactor is open and therefore that batteries are
disconnected from the rest of the battery plant.
2. The yellow “LVD FAIL” LED indicates that only one of
the two redundant low-voltage detectors has directed the
contactor to open and that the disconnect circuit may have
failed. The contactor, however, is still closed.
Fuses F1 through F12 (see Figure 5-1) are also located on the
LVD/Fuse Board and provide power for controller functions and
rectifier regulation. When a fuse blows the colored indicator
(white or orange) pops up and an alarm signal is transmitted to
the controller. The fault should be cleared before replacing a
blown fuse. See “Troubleshooting,” below, for details on
replacing blown fuses.
DC Circuit
Breakers
Circuit breakers CB1 through CB42 are located in the DC
distribution.
Any circuit breaker in the battery plant is ON (or closed) when
the handle is in the Up position, and OFF (or open) in the Down