Chapter 6 Communication Parameter
6-4
6.2 Transmission Standard
In order to use the Cnet I/F module, set the transmission standard like baud rate, data/stop bit. The basic setting
item of Cnet I/F module should be same with transmission standard of system. The written contents are saved in the
CPU module of PLC, those are kept regardless of power supply unit the user write new one.
6.2.1 Setting item
Setting item of Cnet is shown in [Table 6.2.1].
Item
Setting value
Default
Reference
Communication type
RS-232C / RS-422 / RS-485
RS-232C
Setting is essential
Baud rate (bps)
300/600/1,200/1,800/2,400/3,600/4,800/7,200
/9,600/19,200/38,400/57,600/64,000/115,200
9,600
Data
type
Data bit
7/8
8
Stop bit
1/2
1
Parity bit
None/Even/Odd/Ignore
None
Check specific information
Modem type
Null modem / dedicated modem / dial up modem Null modem
Dedicated service
driver
XGT dedicated
XGT server
XGT server
(XGT
dedicated
communication)
Check specific information
Modbus
RTU/ASCII server
Bit read/write area
Word read/write area
Station number
0 ~ 31
0
Commonly used to all
services
[Table 6.2.1] Cnet basic setting item
Since the Cnet I/F module provides two communication channels, Cnet basic setting is necessary for each cannel.
According to communication module, RS-232C 2 ports, RS-232C 1port/RS-422 1 port, RS-422 2 ports is provided.
Additional information of some items in [Table 6.2.1] is as follows.
Summary of Contents for XGL-C22A
Page 172: ...Chapter 8 Modbus Communication 8 23 ...
Page 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Page 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Page 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Page 291: ...Appendix A 25 The lower code shows BCC check setting ...