Chapter 5 System Configuration
5-2
5.1.3 Modem connection to PC & Communication between Cnet I/F modules
(1) PC and Cnet #1 station are connected through modem via RS-232C channel.
(2) Cnet #1 station ~ N station carry out communication between Cnet I/F modules via RS-422 channel.
(3) PC is operated as client station of Cnet #1 station.
(4) Cnet I/F module can connect with max. 32 stations (RS-422/485 communication).
(5) RS-232C channel of Cnet I/F module is set to sever station and RS-422 channel of Cnet I/F module is set to client station.
(6) Dedicated modem or dial-up modem is available to use.
[Fig. 5.1.3] Dedicated modem communication with PC
Type
Module setting
RS-232C
RS-422
Station No.
PLC Cnet #1 station
XGT Server
P2P
1
XGT Client
Cnet #2~#31 station
Not used
XGT Server
2~31
[Table 5.1.1] Module Setting Table for Station No.