Chapter 8 Modbus Communication
8-14
(3) Frame example
Example writing continuous 2 words starting 20
th
address of server 1acting as Modbus RTU mode
Ex.) value to write continuously
Hex
C
D
0
1
0
0
0
A
Address
20
21
(a) Request frame
Classific
ation
Station
no.
Functio
n code
Address
No. of output
Data
size
Output
Error
check
Upper
byte
Lower
byte
Upper
byte
Lower
byte
Frame
01
10
00
13
00
02
04
CD
01
00
0A
CRC
(b) Response frame (In case receiving normal frame)
Classific
ation
Station no.
Function
code
Address
No. of output
Error
check
Upper byte
Lower byte
Upper byte
Lower byte
Frame
01
10
00
13
00
02
CRC
(c) Response frame (In case of receiving abnormal frame)
Classifica
tion
Station no.
Function code
Exceptional code
Error check
Frame
01
90
01
CRC