Chapter 11 Diagnosis
11-4
▶
Loop back test
Check list
Detail result
How to wire the module
< Less than V2.0 > < V2.0 or later >
1. Set actiive mode of test module as server.
2. The RS-422/485 sets a parameter in RS-422.
3. Disable the P2P link of test module.
4. Wire like figure below according to communication port.
(1) RS-232C communication: connect no. 2 with no. 3
(2) RS-422/485 communication: connect TX+ with RX+ and TX- with RX-
5. Select [Online]-[Communication module setting]-[System Diagnosis] or click the icon (
).
6. Click the right button on the the Cnet module and click Loop Back test to check.
Loop Back test
1. Select channel to test and click
‘
Refresh
’