Chapter 2 Product Specifications
2-4
2.4 Cable Specifications
When using communication channel, RS-422 or RS-485, twisted pair cable for RS-422 shall be used in consideration of
communication distance and speed. [Table 2.4] describes recommended specifications of cable. Also when using other cable
than recommended, the cable conforming to characteristics in [Table 2.4] shall be used.
(1) Product : Low Capacitance LAN Interface Cable
(2) Type : LIREV-AMESB
(3) Size : 2P X 22AWG(D/0.254 TA)
(4) Manufacturer: LS Cable
Electric
characteristics
Test item
Unit
Characteristics
Test conditions
Conductor resistance
Ω
/km
59 or less
Normal temp.
Withstanding voltage(DC)
V/1min
Withstands for 1 min. at
500V
In air
Insulation resistance
M
Ω
-km
1,000 or more
Normal temp
Static electricity capacity
pF/M
45 or less
1kHz
Characteristics
impedance
Ω
120
±
12
10MHz
Characteristics of
appearance.
Item
Single Cable
Conductor
Cores
Pair
2
Size
AWG
22
Composition
NO./mm
1/0.643
Outer dia.
mm
0.643
Insulator
Thickness
mm
0.59
Outer dia.
mm
1.94
[Table 2.4.1] Standard of Twisted Pair Cable
[Fig. 2.4.1] Structure
Braided
Ground line
AL/MYLER TAPE
Conductor
Insulator
Sheath
Summary of Contents for XGL-C22A
Page 172: ...Chapter 8 Modbus Communication 8 23 ...
Page 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Page 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Page 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Page 291: ...Appendix A 25 The lower code shows BCC check setting ...