Chapter 10 Program Examples
10-2
10.1.1 In case of acting as server
Sequence
Procedure
Setting method
1
Connection
setting
1. Select [Online]-[Connection Settings] or click icon( )
2. Click [Connect] after setting.
2
Reading I/O
information
Select [Online]-[Diagnosis]-[I/O Information] and click “I/O Sync”.
Reads the information about currently equipped module.
3
Standard
Settings
1. Double-click the relevant Cnet I/F module and execute the standard settings window and
designate the communication type, speed, modem type, data bit, stop bit and station.
2. Modem initialization is available in case of dial-up modem.
3. Response waiting time: waiting time from sending to receiving
(1) Operation setting: Settable in case operation mode is Use P2P.
(2) basic response waiting time per communication speed
(a) 9,600~115,200bps : 100ms+(setting value×100ms)
(b) 7,200~2,400bps : 200ms+(setting value×100ms)
(c) 1,800~1,200bps : 400ms+(setting value×100ms)
(d) 600bps : 800ms+(setting value×100ms)
(e) 300bps : 1,200ms+(setting value×100ms)
4. Delay time setting: sends frame after delay time set by user
(a) Operation setting: settable in case communication type is RS-422/485
5. Delay time between character: In case of character coming within set time at one frame, it means
character interval between character
(a) Operation setting: settable regardless of operation mode
* In case of acting as Modbus ASCII server, data bit should be 7.
Summary of Contents for XGL-C22A
Page 172: ...Chapter 8 Modbus Communication 8 23 ...
Page 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Page 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Page 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Page 291: ...Appendix A 25 The lower code shows BCC check setting ...