Learning Advanced Features
Kinetic Energy Buffering Operation Setting Details
Code
Description
CON-77
KEB Select
Select the kinetic energy buffering operation when the input power is
disconnected.
Setting
Function
0
No
General deceleration is carried out until a low
voltage trip occurs.
1
Yes
The inverter power frequency is controlled
and the regeneration energy from the motor
is charged by the inverter.
CON-78
KEB Start Lev,
CON-79
KEB Stop Lev
Sets the start and stop points of the kinetic energy buffering operation. The
set values must be based on the low voltage trip level at 100%, and the
stop level (CON-79) must be set higher than the start level (CON-78).
CON-80
KEB Slip Gain
Used to prevent malfunctions caused by low voltage from initial kinetic
energy buffering occurring due to power interruptions.
CON-81
KEB P Gain
Used to maintain the voltage during the kinetic energy buffering operation.
It operates the inverter by modifying the set value to prevent malfunctions
caused by low voltage after power interruptions.
CON-82
KEB I Gain
Used to maintain the voltage during the kinetic energy buffering operation.
Sets the gain value to maintain the operation until the frequency stops
during the kinetic energy buffering operation.
CON-83
KEB Acc Time
Sets the acceleration time for the frequency reference when the inverter‘s
operation becomes normal after the kinetic energy buffering operation.
Note
•
The KEB functions may perform differently depending on the size of the loads. The KEB
Gains can be set for a better performance.
•
If a low voltage trip occurs after a power interruption, it indicates the load inertia and level
are high. In such cases, the KEB functions can be performed better by increasing the KEB I
Gain and the KEB Slip Gain.
•
If motor vibration or torque variation occurs during the KEB function operation after power
interruptions, the KEB functions can be performed better by increasing the KEB P Gain or
decreasing the KEB I Gain.
Summary of Contents for LSLV0055H100-4COFN
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...