207
Learning Advanced Features
Code
Description
PRT-73 LDT Dly
Time
Sets the delay time for the operation set at PRT-70.
PRT-74 LDT
Level
Sets the level for the level detection.
The following are the setting ranges and default values by the source.
Source
Default Value
Setting Range
Output
Current
Rated current
0–150% of the rated current
DC Link
Voltage
350
700
0–450 V (2 Type)
0–900 V (4 Type)
Output
Voltage
230
460
0–250 (2 Type)
0–500 (4 Type)
kW
90% of the Inverter
rated power
0–150% of the Inverter rated
power
V1
9.00 V
0.00–12.00
V2
9.00
-12.00–12.00
I2
18.00
0.00–25.00
PID Ref
Value
50
PID Unit Min–PID Unit Max
PID Fdb Val 50
PID Unit Min–PID Unit Max
PID Output 50
-100.00%–100.00%
EPID1 Fdb
Val
50
EPID1 Unit Min–EPID1 Unit Max
EPID2 Fdb
Val
50
EPID2 Unit Min–EPID2 Unit Max
PRT-75 LDT
Band
Width
If the source is detected below the set level, it must be adjusted to be
above the ‗LDT Level + LDT Band Width‘ value to release the level
detection fault trip.
If the source is detected above the set level, it must be adjusted to be
below the ‗LDT Level - LDT Band Width‘ value to release the level detection
fault trip.
The level detection trip bandwidth is 10% of the maximum source value.
PRT-76 LDT
Freq
Sets the start frequency for the level detection. When setting the level
detection frequency, take into consideration the source type and the LDT
level.
PRT-77 LDT
Restart DT
If PRT-08 (RST restart) is set to ‗YES,‘ the inverter restarts after the time set
at PRT-76 elapses when an LDT trip is released. The LDT Restart operates
each time an LDT trip is released.
If PRT-77 is set to any other value than ‗0‘ and the inverter is operating in
HAND mode, the inverter resets and the LDT trip is released. However, the
inverter stays in OFF mode and does not restart the operation instantly.
OUT-31–35
Relay 1–5
Sets one of the output relays to ‗40 (LDT)‘ to monitor the level detection
status.
Summary of Contents for LSLV0055H100-4COFN
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...