RS-485 Communication Features
356
7.3 LS INV 485/Modbus-RTU Communication
7.3.1 Setting Virtual Multi-function Input
Multi-function input can be controlled using a communication address (0h0385). Set codes
COM-70–77 to the functions to operate, and then set the BIT relevant to the function to 1 at
0h0385 to operate it. Virtual multi-function operates independently from IN-65–71 analog
multi-function inputs and cannot be set redundantly. Virtual multi-function input can be
monitored using COM-86 (Virt Dl Status). Before you configure the virtual multi-function
inputs, set the DRV code according to the command source.
Group Code Name
LCD Display
Parameter
Setting
Setting
range
Unit
COM
70–77 Communication multi-
function input x
Virtual DI x(x: 1–8) 0 None 0–55
-
86
Communication multi-
function input monitoring Virt DI Status
- -
-
-
Example:
When sending an Fx command by controlling virtual multi-function input in the
common area via Int485, set COM-70 to ‗FX‘ and set address 0h0385 to ‗0h0001‘.
7.3.2 Saving Parameters Defined by Communication
If you turn off the inverter after setting the common area parameters or keypad parameters
via communication and operate the inverter, the changes are lost and the values changed
via communication revert to the previous setting values when you turn on the inverter.
Set CNF-48 to ‗1 (Yes)‘ to allow all the changes over comunication to be saved, so that the
inverter retains all the existing values even after the power has been turned off.
Setting address 0h03E0 to ‗0‘ and then setting it again to ‗1‘ via communication allows the
existing parameter settings to be saved. However, setting address 0h03E0 to ‗1‘ and then
setting it to ‗0‘ does not carry out the same function.
Summary of Contents for LSLV0055H100-4COFN
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...