Learning Protection Features
322
Group Code Name
LCD Display
Parameter
Setting
Setting
range
Unit
36
Multi-function output 1
item
Q1 Define
Overload Early Warning and Trip Setting Details
Code
Description
PRT-17
OL Warn Select
If the overload reaches the warning level, the terminal block multi-function
output terminal and relay are used to output a warning signal. If ‗1 (Yes)‘ is
selected, it will operate. If ‗0 (No)‘ is selected, it will not operate.
PRT-18
OL Warn Level,
PRT-19
OL Warn Time
When the input current to the motor is greater than the overload warning
level (OL Warn Level) and continues at that level during the overload
warning time (OL Warn Time), the multi-function output (Relay 1, Q1)
sends a warning signal. When Over Load is selected at OUT-31, OUT-33,
the multi-function output terminal or relay outputs a signal. The signal
output does not block the inverter output.
PRT-20
OL Trip Select
Select the inverter protective action in the event of an overload fault trip.
Setting
Function
0 None
No protective action is taken.
1 Free-Run
In the event of an overload fault, inverter output is
blocked and the motor will free-run due to inertia.
3 Dec
If a fault trip occurs, the motor decelerates and stops.
PRT-21 OL Trip
Level,
PRT-22 OL Trip
Time
When the current supplied to the motor is greater than the preset value of
the overload trip level (OL Trip Level) and continues to be supplied during
the overload trip time (OL Trip Time), the inverter output is either blocked
according to the preset mode from PRT-17 or slows to a stop after
deceleration.
Summary of Contents for LSLV0055H100-4COFN
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...