Chapter 5 Profibus-DP Communication
5-36
(6) Communication module and Communication period setting
If double-click the High-speed link, screen of Communication module settings and Communication cycle settings
is opened. In this screen, communication module, communication and Output data setup in case of emergency
settings period can be specified.
High Speed Link setting initial screen
Items
Description
Communication
module settings
Module
type
Setting of communication module installed
Applicable module: FENet, FDEnet, Dnet, Rnet, Pnet
Base No.
Setting of base position installed (Maximum 7 bases allowed)
Range of Setting: 0 ~ 7
Slot No.
Setting of slot position installed (Maximum 12 slots allowed)
Range of Setting: 0 ~ 11
Communication period
settings
Period type
- It is set to transmit the data time every period.
- Range of setting: 20
㎳
, 50
㎳
, 100
㎳
, 200
㎳
, 500
㎳
, 1s, 5s, 10s
(default is 20
㎳
)
- But Receive data will be updated data in every scan regardless of
communication period.
- Communication period will be applied to all of the Send/Receive blocks.
Output
data setup
in case of
emergency
settings
CPU
error
Latch
- Keep the output (But, Clear the P device data)
Clear
- Clear the all data
CPU stop
Latch
- Keep the output (But, Clear the P device data)
Clear
- Clear the all data
Setting of communication module
Summary of Contents for XGL-PSEA
Page 1: ...Programmable Logic Control Pnet Slave I F Module XGL PSRA XGL PSEA XGT Series ...
Page 13: ...Table of Content 12 ...
Page 25: ...Chapter 1 Overview 1 12 ...
Page 31: ...Chapter 2 Product Specification 2 6 ...
Page 41: ...Chapter 3 System Configuration 3 10 ...
Page 61: ...Chapter 4 Communication Programming 4 20 ...
Page 150: ...Appendix A 13 A 2 Dimension XGL PSEA XGL PSEA ...
Page 151: ...Appendix A 14 ...
Page 153: ...Warranty and Environment Policy 2 ...