Appendix
A-9
A.1.2 List of Communication Relays (L)
- Special register for data
* HS link No. 1
No.
Keyword
Type
Detail
Description
L000000 _HS1_RLINK
Bit
HS link parameter No.1’s all stations
normally operated
Displays all stations normally operated as specified in HS link parameter,
which will be On if
1.There is no error with all stations specified in
parameter in RUN mode
2. All data block is in normal communication as
specified in parameter.
3. The parameter specified in each station itself is
in normal communication. Run_link will be kept
On if once On until stopped by link disenable.
L000001 _HS1_LTRBL
Bit
After _HS1RLINK is ON, abnormal
status displayed
This flag will be On if the station specified in
parameter and the data block’s communication
status are as described below with _HSmRLINK
flag On,.
1. when the station specified in parameter is not in RUN mode,
2. when the station specified in parameter is in
error,
3. when data block’s communication status
specified in parameter is unstable,
The link trouble will be On if one of those
conditions 1,2 and 3 above occurs. And if such a
condition is back to normal, it will be Off.
L000020 ~
L00009F
_HS1_STATE[k]
(k=000~127)
Bit
Array
HS link parameter No.1, Block No.k’s
general status
displayed
Displays the general status of the communication information for the
specified parameter’s respective data blocks.
HS1STATE[k]=HS1MOD[k]&_HS1TRX[k]&(~_HSmERR[k])
L000100 ~
L00017F
_HS1_MOD[k]
(k=000~127)
Bit
Array
HS link parameter No.1, Block No.k
station’s Run
operation mode
Displays the operation mode of the station
specified in parameter’s data block k.
L000180 ~
L00025F
_HS1_TRX[k]
(k=000~127)
Bit
Array
Normal communication displayed with
HS link parameter
No.1, Block No.k station
Displays the communication sta
tus of parameter’s data block k to check
if normal as specified.
L000260 ~
L00033F
_HS1_ERR[k]
(k=000~127)
Bit
Array
HS link parameter No.1, Block No.k
station’s Run error mode
Displays the communication status of parameter’s data block k to check
for any error.
L000340 ~
L00041F
_HS1_SETBLOCK
[k=000~127]
Bit
Array
HS link parameter No.1, Block No.k
setting displayed
Displays the setting status of parameter’s data block k.
[Table A.1] List of communication flags based on HS link number
K as a block number is displayed through 8 words by 16 for 1 word for the information of 128 blocks from 000 to 127.
For example, block information of 16~31, 32~47, 48~63, 64~79, 80~95, 96~111, 112~127 will be displayed in L00011,
L00012, L00013, L00014, L00015, L00016, L00017 from block 0 to block 15 for mode information (_HS1MOD).
* High speed link number 2~12
HS link No.
L area address
Remarks
2
L000500~L00099F
Compared with HS link of 1 in [Table 1], other HS link station
number’s flag address will be simply calculated as follows;
Calculation formula: L area address = L 500 x (HS link
No.
– 1)
In order to use HS link flag for program and monitoring, use the flag
map registered in XG5000 for convenient application.
3
L001000~L00149F
4
L001500~L00199F
5
L002000~L00249F
6
L002500~L00299F
7
L003000~L00349F
8
L003500~L00399F
9
L004000~L00449F
10
L004500~L00499F
11
L005000~L00549F
[Table 2] Relation between high speed link and L device
Summary of Contents for XGL-PSEA
Page 1: ...Programmable Logic Control Pnet Slave I F Module XGL PSRA XGL PSEA XGT Series ...
Page 13: ...Table of Content 12 ...
Page 25: ...Chapter 1 Overview 1 12 ...
Page 31: ...Chapter 2 Product Specification 2 6 ...
Page 41: ...Chapter 3 System Configuration 3 10 ...
Page 61: ...Chapter 4 Communication Programming 4 20 ...
Page 150: ...Appendix A 13 A 2 Dimension XGL PSEA XGL PSEA ...
Page 151: ...Appendix A 14 ...
Page 153: ...Warranty and Environment Policy 2 ...