Chapter 8 Trouble Shooting
8-19
10)
Module detachment diagnostic message
Error information of module operates as Pnet standard id diagnosis message. Now, ID diagnosis data field consists
of 3 byte. First byte means it is ID diagnosis field. Second and third bytes mean the slot number of module where
diagnosis occurs. Configuration of 3 byte is as follows.
0100 0011
Second byte: means from 0
th
slot to 7
th
slot
Third byte: means from 8
th
slot to 12
th
slot
(1) PSRA supports both channel and ID diagnostic message. We assume that module detachment occurs at 11
th
and 12
th
slot and channel disconnection occurs at CH8 of 6
th
slot analog module.
In normal data communication status, no message appears as figure above. If situation described above occurs,
diagnostic message is displayed as follows. In case of module detachment, you should reset PSRA to return to
data communication status. If you detach module by using module change switch, it is not considered as
diagnostic message.