Chapter 5 Profibus-DP Communication
5-31
The High-speed Link item tab of the above figure means max. installation number of communication module
according to PLC CPU type. The High-speed Link button as much as the available setting number shall be
active and in this case, the High-speed Link no. is not related to the installed slot no. and the slot no. shall be set
in the individual parameter setting screen and only one High-speed Link parameter is available to set for one
communication module.
The following table shows the communication model available to install per MASTER-K CPU model and max.
installation number.
Max. installation number per MASTER-K CPU model
Classification
Available communication module
Max. installation number
Remarks
K1000S CPU
G3L-PUEA, G3L-PUEB
4
-
K300S CPU
G4L-PUEA, G4L-PUEB
2 /4 (Above version 3.0)
K200S CPU
G6L-PUEA, G6L-PUEB
2
* If combined with other communication module using the High-speed Link, the installation number shall be limited.
a) Link: This is the item to allow the High-speed Link and the initial value is prohibited and it is required to set ‘enable’ to
execute the High-speed Link.
b) Self station no. : Master module is set in SyCon and the slave module is set as rotary switch. It is not available to
change here.
c) Base: It sets the base position that the communication module to set is installed.
d) Slot: It sets the position that the communication module to set is installed. (0 ~ 7 slot).
e) Type: It sets the type of the installed communication module and sets the Pnet.
3)
Parameter setting and modification
If you double-click the corresponding parameter from the parameter setting basic screen as shown on the figure
below, the High-speed Link parameter setting screen will appear.
a) area: When sending, set the area to read the data to send and set the storage area of the received data when
receiving.
b) Size: This means the data size to send/receive and the unit is 1 byte and it is available to set total sending/receiving
as 1Kbytes for G3/4/6L-PUEA and 7Kbytes for G3/4/6L-PUEB
Summary of Contents for XGL-PSEA
Page 1: ...Programmable Logic Control Pnet Slave I F Module XGL PSRA XGL PSEA XGT Series ...
Page 13: ...Table of Content 12 ...
Page 25: ...Chapter 1 Overview 1 12 ...
Page 31: ...Chapter 2 Product Specification 2 6 ...
Page 41: ...Chapter 3 System Configuration 3 10 ...
Page 61: ...Chapter 4 Communication Programming 4 20 ...
Page 150: ...Appendix A 13 A 2 Dimension XGL PSEA XGL PSEA ...
Page 151: ...Appendix A 14 ...
Page 153: ...Warranty and Environment Policy 2 ...