TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PROTECTION CONTROL
Pressure Protection Control
Pressure Protection Control
Pressure Control in Cooling Mode
Pressure Range
Compressor
Fan
3GSVL
Stop
Stop
Pd > 547.5 psi
-15 Hz / 10 seconds
530VHFRQGV
3GSVL
Frequency Hold*
530VHFRQGV
3GSVL
+]RUOHVVVHFRQGV
530VHFRQGV
Pd < 504.7 psi
Normal Control
Table 12: High Pressure Control in Cooling Mode.
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
Table 13: Low Pressure Control in Cooling Mode.
Pressure Range
Compressor
Fan
3VSVL
Stop (one [1]) minute later)
Stop
3VSVL
-15 Hz / 10 seconds
-100 RPM / 10 seconds
Ps > 21.8 psi
Frequency Hold*
-100 RPM / 10 seconds
Ps > 23.2 psi
+]RUOHVVVHFRQGV
-100 RPM / 10 seconds
Ps > 27.6 psi
+]RUOHVVVHFRQGV
-100 RPM / 10 seconds
Ps > 31.9 psi
Normal Control
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
Pressure Control in Heating Mode
Pressure Range
Compressor
Fan
3GSVL
Stop
Stop
Pd > 495.3 psi
-15 Hz / 10 seconds
-50 RPM / 10 seconds
Table 14: High Pressure Control in Heating Mode.
Table 15: Low Pressure Control in Heating Mode.
Pressure Range
Compressor
Fan
3VSVL
Stop
Stop
3VSVL
-15 Hz / 10 seconds
530VHFRQGV
3VSVL
Frequency Hold*
530VHFRQGV
3VSVL
+]RUOHVVVHFRQGV
530VHFRQGV
3VSVL
Normal Control
Normal Control
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).