Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Cause Check
Checklist
App.
Check Point
Normal
Abnormal
Defective
Parts
External Noise
Wrong Connection
0DVWHU2'8ļ
Slave ODU)
Push the reset button (If the cause in
noise, communication will fail
intermittently.
Check if shielded wire is used or not.
Wire
Shield wire
Non-shielded wire
Wire /
External Noise
B4
(Power Off)
Check connection of GND wire from
chassis
Wire
Connected
from chassis
Non connected
from chassis
-
Check whether wiring A and B is incorrect.
0DVWHU2'8ļ6ODYH2'8
ODU A,B
Terminal Block
A-A, B-B
Cross connect A
with B
-
SMPS PCB
Damaged
Check 5V Voltage (Comm. 5V)
Voltage
4.5V ~ 5.5V
9Ļ
SMPS PCB
A4
(Power On)
Check Resistance of Communication IC
Resistance
NĹ
NĻa
Main PCB
B4
(Power Off)
External PCB
Damaged
Check whether patterns in external PCB
are connected
Resistance
Ļ
Open
External PCB
Table 82: Error No. 104 Improper Connections Checkpoint Details.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 104, continued.
Master
Slave
SODU Comm. B
SODU
B
SODU
A
SODU
B
SODU
A
SODU Comm. A
NG
Figure 74: Error No. 104 Improper Connections.
Figure 75: Checking Error No. CH104 from Main PCB (Communication IC) In Case of Power Off.
Red
Black
Figure 76: Multi-Meter (Note the
Probe Color).
+%%
Table 83: Error No. 104 Main PCB (Communication IC) Checkpoint Details.
Check
Mode
Multi-Meter
Measured Value
Black
Red
Normal
Abnormal
IC07C
ȍ
IC07C GND (pin 5) IC07C Vcc (pin 8)
NĹ
Not Normal