![LG Multi V 5 Service Manual Download Page 178](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770178.webp)
178
MUL
TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 79
Error No.
Description
Details
Causes
79
Master: 791
Slave 1: 792
Slave 2: 793
Outdoor unit fan
operation error.
Outdoor unit fan motor is experiencing first
position sensor failure.
1. Fan motor is defective or the assembly is
not correct.
2. Fan motor has disconnected (U,V,W out-
put).
3. Fan PCB is defective.
Is the fan motor assembly
correct?
Check if the outdoor unit fan motor assembly is
correct or if it is locking up.
ĺ5HDVVHPEOHRUUHSODFHLIHUURUVDUHIRXQG
No
Yes
Are the fan motor connections
correct?
No
The resistance between
each phase, and the insulation
resistance of the motor output
terminal correct?
1. Check the resistance between each motor output terminal.
2. Check insulation resistance between the outdoor unit fan motor termi-
nals (U,V,W) and the pipe (>100M).
ĺ5HSODFHIDQPRWRULIHUURUVDUHIRXQG
No
Yes
Recheck power and installation.
1. Check if the color of the motor output terminal
(U,V,W) connections match the PCB connections.
2. Check for wiring damage, or if the wiring has discon-
nected.
ĺ5HDVVHPEOHRUUHSODFHLISUREOHPVDUHIRXQG
Is the fan PCB assembly
correct?
Yes
Yes
No
Check if the fan PCB assembly IPM is correct.
ĺ5HSODFHIDQ3&%DVVHPEO\LIHUURUVDUH
found.
Small Frame
Large Frame
Power Supply
208V/230V,
60Hz,
3-phase
460V,
60Hz,
3-phase
208V/230V,
60Hz,
3-phase
460V,
60Hz,
3-phase
Rating Output
1,500 W
1,200 W
900 W
900 W
Motor Resistance
at 167°F
ȍ ȍ ȍ ȍ