ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 57
Error No.
Description
Details
Causes
57
Master: 571
Slave 1: 572
Slave 2: 573
Communication
error between
outdoor unit main
PCB and inverter
PCB.
Outdoor unit inverter PCB is not receiving
signal from main PCB.
1. Bad connection between main and inverter
PCBs.
2. Communication wire noise effect.
3. The outdoor unit main PCB is damaged.
4. The outdoor unit inverter PCB is
damaged.
Are the communi-
cation cable connections
correct?
Recheck power and installation.
1. Check communication wiring.
2. Check connections.
ĺ5HZLUHLIHUURUVDUHIRXQG
No
Yes
After resetting the
power, does the error still
display?
Yes
No
Replace main PCB.
Is the inverter PCB
assembly correct?
Replace Inverter PCB.
No
Yes
Communication
LED
Communication
LED
Communication
LED
Communication LED
Fan Board
Inverter Compressor
PCB 1
Inverter Compressor
PCB 2
Main PCB