Error No. 34
Error No.
Description
Details
Causes
34
Master: 341
Slave 1: 342
Slave 2: 343
Outdoor unit
compressor high
pressure safety
tripped.
System shut off be-
cause of an excessive
increase in pressure
at the outdoor unit
that occurred ten (10)
consecutive times.
1. Shutdown due to if one compressor’s high pressure is >4,000 kPa
(580 psi) for ten (10) seconds.
2. Defective high pressure sensor.
3. Defective indoor unit and / or outdoor unit fan.
4. Refrigerant is overcharged.
5. Refrigerant pipe is damaged.
6. Defective indoor and / or outdoor unit EEV.
7. Outdoor unit is blocked during cooling, or indoor unit filter is
blocked during heating.
8. Service valve is clogged.
9. Defective outdoor unit PCB.
10. Defective indoor unit pipe temperature.
11. Defective indoor unit pipe temperature sensor.
12. Defective hot gas valve.
Is the service valve open?
No
Open the service valve.
Are the communication
cable and piping
connections correct?
Yes
No
Is the amount of
refrigerant appropriate
to the system?
Yes
No
Are the fans operating
correctly (indoor fan
during heating; outdoor
fan during cooling)?
Yes
No
Yes
Add or subtract refrigerant.
Check and repair communication
cable and piping connections.
Replace fan components (refer to
Error Nos. 105~107).
Are any components
blocked? Heating: indoor unit
filter; cooling: outdoor unit
heat exchanger.
No
Clean indoor unit filter (heating) and /
or outdoor unit heat exchanger
(cooling)?
Is the value of the high
pressure sensor the same
as the manifold value?
No
Replace high pressure sensor.
Yes
Yes
Check indoor unit EEV, indoor
unit PCB, and indoor / outdoor
unit installation.