![LG Multi V 5 Service Manual Download Page 175](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770175.webp)
175
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 71
Error No.
Description
Details
Causes
71
Master: 711
Slave 1: 712
Slave 2: 713
Outdoor unit
converter CT
sensor error.
MICOM input voltage isn’t within 2.5V±0.3V at
initial power up.
1. Input voltage is not correct (R-T).
2. Damage to the outdoor unit converter PCB
(CT sensor component).
Are the power wiring
connections correct?
1. Check R / S / T / N wiring connections
2. Check noise filer wiring connections.
ĺ5HZLUHLISUREOHPVDUHIRXQG
No
Yes
Is the converter PCB
assembly correct?
No
Is the input voltage
normal?
1. Check if R-T / T-S / S-T phase voltage is
208-230V ± 10% or in the 414-528V range for
460V.
2. Check wiring and connections.
No
Yes
Yes
Recheck power and installation.
Replace converter PCB.
Converter PCB Assembly.
Measure Input Voltage.
Images here are representative of system
components. Actual component appearance