151
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 26
Error No.
Description
Details
Causes
26
Master: 261
Slave 1: 262
Slave 2: 263
Outdoor unit in-
verter compressor
operation error.
Inverter compressor start failure.
1. Overload error: Piping is clogged, indoor or
outdoor unit is blocked, EEV is blocked, or
there is an overcharge in refrigerant.
2. Compressor insulation and / or motor has
been damaged.
3. Compressor wiring error.
4. Outdoor unit inverter PCB has been dam-
aged (CT).
Is the installation correct?
Recheck power and installation.
1. Check if piping is clogged or has been damaged.
2. Check if outdoor or indoor units are blocked.
3. Check if EEV is operating normally and the connections are cor-
rect.
4. Check the refrigerant pressure.
ĺ5HLQVWDOORUIL[LIHUURUVDUHIRXQG
No
Yes
Yes
Are the power wiring
connections correct?
Is the resistance be-
tween each phase and the
Inverter compressor insulation
resistance correct?
Yes
No
No
1. Check the resistance between each compressor terminal.
2. Check insulation resistance between compressor terminal and pipe
!ȍ0
ĺ5HSODFHFRPSUHVVRULIHUURUVDUHIRXQG
Is the Inverter
compressor PCB assembly
correct?
Are the compressor wiring
connections correct?
Check R(L1) / S(L2) / T(L3) wiring connections.
ĺ5HZLUHLIHUURUVDUHIRXQG
1. Check Inverter compressor PCB assembly, U,V,W connections.
2. Check if the wires have disconnected or were damaged.
3. Check compressor terminal connections for bad contacts.
ĺ5HDVVHPEOHLIHUURUVDUHIRXQG
Check if Inverter compressor PCB assembly and IPM are correct.
ĺ5HSODFHFRPSUHVVRU3&%DVVHPEO\LIHUURUVDUHIRXQG
Yes
No
Yes
No
JQC068MA
Temp.
77°F
167°F
U-V
ȍ ȍ
V-W
ȍ ȍ
W-U
ȍ ȍ
JQC048MA
Temp.
77°F
167°F
U-V
ȍ ȍ
V-W
ȍ ȍ
W-U
ȍ ȍ
JQC068MB / JQC068MBA
Temp.
77°F
167°F
U-V
ȍ ȍ
V-W
ȍ ȍ
W-U
ȍ ȍ
JQC048MB / JQC048MBA
Temp.
77°F
167°F
U-V
ȍ ȍ
V-W
ȍ ȍ
W-U
ȍ ȍ