roubleshooting Main Components
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
:KHQPHDVXULQJYROWDJHDQGFXUUHQWRILQYHUWHUSRZHUFLUFXLWYDOXHVZLOODSSHDUGLႇHUHQWO\GHSHQGLQJRQWRROVDQGFLUFXLWV
because voltage, power supply current, or inverter output has no sine waveform. Also, output voltage changes when inverter
output voltage has a pulse wave pattern.
1. If using a movable tester to check if inverter output voltage is constant (when comparing relative voltage between lines), always use an analog me-
ter. Exercise particular caution if the inverter output frequency is low, when using a tester, where the change of measured voltage values is large
EHWZHHQRWKHUOLQHVZKHQYLUWXDOO\WKHVDPHYDOXHVDSSHDURULQVLWXDWLRQVZKHUHLWFDQEHGLI¿FXOWWRGHWHUPLQHLIDQLQYHUWHUIDLOHG
2.
8VHDUHFWL¿HUYROWPHWHULIXVLQJDFRPPHUFLDOIUHTXHQF\WHVWHUWRPHDVXUHLQYHUWHURXWSXWYDOXHVZKHQPHDVXULQJDEVROXWHYDOXHV
Accurate measuring values cannot be obtained with a general movable tester (for analog and digital mode).
Checking the Outdoor Unit Fan
If there is a fan error, check the items below and follow the corresponding procedure listed.
Check
Problem
Solution
1. Fan motor is not
operating. (Does
fan motor fail
again when opera-
tion starts?)
2. Fan motor
vibration is exces-
sive.
Power supply is not
correct.
Check wire connections at the breaker.
Modify the power supply voltage if it is beyond permissible specifications.
Wiring is wrong.
• Check wiring connections.
• Check connector contacts.
• Check that all components are firmly secured (tighten screws).
• Check polarity connection.
• Check ground wiring and for short circuits.
Motor has failed.
Measure the winding resistance of the motor coils.
Fuse is defective.
Replace the fuse.
Circuit board is
defective.
Replace the circuit board following the steps below if errors occur again after resetting the
power, and if there are no errors similar to those specified above.(Carefully check both connec-
tor and ground wires when replacing the circuit board.)
• Replace only the fan control board. If operation begins, then the fan control board was
defective.
• Check and replace inverter board and / or main board if fan operation continues to fail.
• If problems continue to occur even after following the procedures above, then both boards
are defective.
Small Frame
Large Frame
Power Supply
208V/230V, 60Hz,
3-phase
460V, 60Hz,
3-phase
208V/230V, 60Hz,
3-phase
460V, 60Hz,
3-phase
Rating Output
1,500 W
1,200 W
900 W
900 W
Motor Resistance
at 167°F
ȍ
ȍ
ȍ
ȍ
CHECKING THE OUTDOOR UNIT FAN