ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 151
Error No.
Description
Details
Causes
151
Master: 1511
Slave 1: 1512
Slave 2: 1513
The difference
between the high
and low pressure
is too low.
Not enough pressure difference between high
and low. Function error of outdoor unit four-
way reversing valve.
1. Problem with four-way valve operation
because of sludge, inflow, etc.
2. No pressure difference because of
compressor error.
3. Defective four-way valve (resistance is not
ȍ
Is the four-way valve con-
nected properly?
Reconnect the four-way valve.
No
Yes
Is the four-way
valve coil resistance normal
ȍ"
No
Change the four-way valve coil.
Yes
Is the four-way valve
coil connected to the four-way
valve correctly?
Yes
No
Re-insert four-way valve coil.
If there are more than
two outdoor units, does the
master outdoor unit recognize
all the slave units?
After power is reset
and heating mode begins,
can supply voltage be verified
at the PCB?
Is the compressor operat-
ing normally?
After the mode is
change from cooling to
heating or vice versa, does the
same error occur again?
No
See Error No. 51.
No
Replace outdoor unit PCB.
No
No
Yes
Yes
Yes
Replace the four-way valve.
Replace 4 way valve.
Yes
Check and replace compressor (magnet switch,
corresponding PCB, see electric components).
To get the valve to switch, close the outdoor unit hot gas service valve,
then put the system in heat mode, and if pressure builds, slowly open
the hot gas valve.