![LG Multi V 5 Service Manual Download Page 172](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770172.webp)
172
MUL
TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 62
Error No.
Description
Details
Causes
62
Master: 621
Slave 1: 622
Slave 2: 623
High temperature
at the outdoor unit
inverter PCB heat
sink.
Heatsink temperature is >257°F.
1. Inverter PCB IGBT / IPM connection is not
correct.
2. Outdoor unit fan motor operation is
malfunctioning.
3. Outdoor unit inverter PCB assembly is
defective.
4. Overload operation (pipe is clogged, fan is
blocked, EEV is defective, overcharge in
refrigerant).
Check Inverter PCB Connection Installation
Images here are representative of system
components. Actual component appearance
depends on model and system type.
Is the installation correct?
1. Check piping for clogs or damage.
2. Check if the outdoor unit or indoor unit air flow is blocked.
3. Check EEV connections / assembly / or if the EEV is operating normally.
4. Check refrigerant pressure
5. Check power wiring to see if it is connected properly or is damaged.
ĺ5HDVVHPEOHRUVHUYLFHLIHUURUVDUHIRXQG
No
Yes
Is the outdoor unit
fan motor operating
normally?
Yes
No
Check the outdoor unit fan motor operation and / or if it is locked up.
ĺ5HDVVHPEOHRUVHUYLFHLIHUURUVDUHIRXQG
Is the inverter PCB IPM con-
nection correct?
Check inverter PCB connections.
ĺ5HFRQQHFWLIHUURUVDUHIRXQG
No
Yes
Is the inverter PCB
assembly correct?
Yes
Recheck power and installation.
No
Replace inverter PCB assembly.
Always apply heat transfer paste to the new
inverter PCB heat sink before installing. For
instructions, see “Replacing the Inverter PCB
Heat Sink” page later in this section.