ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 193
Error No.
Description
Details
Causes
193
Master: 1931
Slave 1: 1932
Slave 2: 1933
Excessive in-
crease in outdoor
unit fan PCB heat
sink temperature.
System has shut off because outdoor unit fan
PCB heat sink temperature is >194°F.
1. Fan PCB IPM connection is not correct.
2. Outdoor unit fan motor is not operating
correctly.
3. Outdoor unit fan PCB assembly is
defective.
4. Overload operation (piping is clogged, fan
is blocked, EEV is defective, overcharge in
refrigerant).
Has the system been
installed correctly?
1. Check if any pipes are clogged or damaged.
2. Check if the outdoor or indoor unit fans are blocked.
3. Check EEV assembly; if it is connected or is operating
normally.
4. Check refrigerant pressure.
5. Check power wiring connections. Reconnect or rewire if
problems are found.
No
Yes
Is the fan PCB IPM
connected correctly?
No
Recheck power and installation.
Check fan PCB connection. Reconnect or rewire if errors
are found.
Yes
Is the outdoor
unit fan motor operating
normally?
Yes
No
Check the outdoor unit fan motor operation, or if
the fan has locked up. Fix if errors are found.
Is the fan PCB assembly
correct?
Replace fan PCB assembly.
No
Yes
Check fan connection installation.