Troubleshooting Guide
- 82 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
CN-REMO
: Remote controller connection
❇
The PCB can differ from model to model.
Check from the right source.
Checking communication cable connection status
Does the error happens
again if the remote
controller is replaced?*
Does the error occurred
when the cable of remote
controller is replaced?
Replace cabled remote
controller
Check connection &
communication cable **
Replace indoor unit PCB ***
Yes
Yes
No
No
03 No communication between cabled
remote controller & indoor unit
Error
No.
Error Type
Error Point
Main Reasons
The remote controller
did not receive the sig-
nal from indoor unit
during specific time
1. Remote controller fault
2. Indoor unit PCB fault
3. Connector fault, Wrong connection
4. Communication cable problem
n
Error diagnosis and countermeasure flow chart
* If there is no remote controller to replace : Use another unitʼs remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
‘
make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Summary of Contents for ARNU05GL1G2