3. Self-diagnosis function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
- 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number. Indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
1051 : No.105 error of master unit
h
Refer to the DX-Venitilation manual for DX-Venitilation error code
Display
Title
Cause of Error
Indoor unit related error
0
1
- Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
0
2
- Inlet pipe temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
0
3
-
Communication error : wired remote
controller
÷
indoor unit
Failing to receive wired remote controller signal in indoor unit
PCB
0
4
- Drain pump
Malfunction of drain pump
0
5
-
Communication error : outdoor unit
÷
indoor
unit
Failing to receive outdoor unit signal in indoor unit PCB
0
6
- Outlet pipe temperature sensor of indoor unit
Outlet pipe temperature sensor of indoor unit is open or short
0
9
- Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1
0
- Poor fan motor operation
Disconnecting the fan motor connector/Failure of indoor fan
motor lock
1
7
- Inlet Air temperature sensor of FAU
Air temperature sensor of indoor unit is open or short
Outdoor unit related error
2
1
1 Master Outdoor Unit Inverter Compressor IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 Slave1 Outdoor Unit Inverter Compressor IPM Fault
Slave1 Outdoor Unit Inverter Compressor Drive IPM Fault
3 Slave2 Outdoor Unit Inverter Compressor IPM Fault
Slave2 Outdoor Unit Inverter Compressor Drive IPM Fault
4 Slave3 Outdoor Unit Inverter Compressor IPM Fault
Slave3 Outdoor Unit Inverter Compressor Drive IPM Fault
2
2
1
Inverter Board Input Over Current(RMS) of
Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current excess (RMS)
2
Inverter Board Input Over Current(RMS) of
Slave1 Outdoor Unit
Slave1 Outdoor Unit Inverter Board Input Current excess (RMS)
3
Inverter Board Input Over Current(RMS) of
Slave2 Outdoor Unit
Slave2 Outdoor Unit Inverter Board Input Current excess (RMS)
4
Inverter Board Input Over Current(RMS) of
Slave3 Outdoor Unit
Slave3 Outdoor Unit Inverter Board Input Current excess (RMS)
(repetition)
Error Compressor
Error number
Unit (1 : Master, 2 : Slave1, 3 : Slave2, 4 : Slave3)
Self-diagnosis function