Troubleshooting Guide
- 135 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
n
Error diagnosis and countermeasure flow chart
n
Check Fan PCB Screw Connection Condition
Error No.
Error Type
Error Point
Main Reasons
193*
Master
1931
Slave1
1932
Slave2
1933
Slave3
1934
Fan PCB Heatsink
Temperature High
Heatsink Temperature
is Over 90°C
1. Fan PCBA IPM Connection Condition Abnormal
2. Outdoor Unit Fan Motor Operation Abnormal
3. Outdoor Unit Fan PCB Assembly Defect
4. Overload Operation (Pipe Clogging/ Covering/EEV
Defect/Ref. Overcharge)
Is Installation
Condition Normal?
No
1. Check Pipe Clogging/ Distortion
2. Check Covering (Outdoor/Indoor Unit)
3. Check EEV Connector Assemble Condition/Normal Operation
4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Reassemble or Manage if abnormality Found
1. Check Fan PCBA Screw Connection Condition
Reassemble or Manage if abnormality Found
No
Fan PCB IPM Connection
Condition Normal?
Yes
1. Check Outdoor Unit Fan Motor Operation or Lock
Reassemble or Manage if abnormality Found
No
Is ODU Fan Motor Normal?
Yes
1. Reset
Replace Fan PCB Assembly
No
Is Fan PCB assembly
Normal?
Yes
Recheck Power and
Installation Condition
Yes
Check Screw Connection Condition
Summary of Contents for ARNU05GL1G2