Function
3.2 Discharge temperature control
n
Outdoor unit control
SC : Sub Cooling, SH : Super Heating
3.3 Inverter protection control
h
AC input current is input current of inverter compressor except constant current (current pass through noise filter)
OFF
SC,SH decrease control
SH decrease control
Normal control
SC,SH decrease control
SH decrease control
-5Hz/10sec.
SC,SH decrease control
SH decrease control
Temperature range
Compressor
Sub cooling EEV
IDU EEV
Tdis >110℃
Tdis >100℃
Normal control
SC,SH decrease control
SH decrease control
Tdis≤ 100℃
Frequency holding
SC,SH decrease control
SH decrease control
Tdis≥ 105℃
Tdis >108℃
Compressor Current
AC Input Current
Cooling mode
Heating mode
Compressor Current
AC Input Current
4.8Hp
6.8Hp
4.8Hp
6.8Hp
4.8Hp
6.8Hp
22A or less
30A or less
22A or more
30A or more
22A or more
32A or more
24A or less
35A or less
24A or more
35A or more
30A or more
41A or more
4.8Hp
6.8Hp
4.8Hp
6.8Hp
4.8Hp
6.8Hp
22A or less
30A or less
22A or more
30A or more
22A or more
32A or more
26A or less
35A or less
26A or more
35A or more
30A or more
41A or more
System Stop
System Stop
Normal Operation
Frequency Down
Normal Operation
Frequency Down