Troubleshooting Guide
- 117 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
n
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Is the value of temperature
sensor resistance normal?*
Check and correct connection
Replace sensor
Replace outdoor unit PCB
Yes
Yes
No
No
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
Error No.
Error Type
Error Point
Main Reasons
65*
Master
651
Slave1
652
Slave2
653
Slave3
654
Outdoor unit liquid
pipe (condenser) tem-
perature sensor error
Abnormal sensor resis-
tance value
(Open/Short)
1. Defective temperature sensor connection
2. Defective temperature sensor (Open / Short)
3. Defective outdoor unit PCB