- 48 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
4.17 Cycle Data View
This function is intended to identify the Cycle data of ODU, which is running on.
The 7 Segment is display 26 different cycle data.
Master unit PCB DIP switch on : No.5
Cycle data view function setting method
Select the mode using
‘
ȯ
’
,
‘
ȭ
’
Button : “SVC”
Push the
‘
●
’
button
Select the Function using
‘
ȯ
’
,
‘
ȭ
’
Button : : “Se3”
Push the
‘
●
’
button
Selec the Option using
‘
ȯ
’
,
‘
ȭ
’
Button : : “op1~op26”
Push the
‘
●
’
button
Start the Cyce data view fuction : Display the cycle
data value selected from the Segment.
step
Title
7-seg
example
seg_1
seg_2
seg_3
seg_4
op1
Current High Pressure
P1
4321kPa
4
3
2
1
op2
Current low Pressure
P2
1234kPa
1
2
3
4
op3
Inv 1 Pulse
h1
120
1
2
0
op4
Inv 2 Pulse
h2
30
3
0
op5
fan rpm
h3
110
1
1
0
op6
Subcooling degree
T1
5.3
5
3
op7
Superheating degree
T2
-4.5
-
4
5
op8
ODU temp.
T3
10
1
0
0
op9
Suctino temp.
T4
43.4
4
3
4
op10
Comp1 discharge temp.
T5
150
1
5
0
op11
Comp2 discharge temp.
T6
124
1
2
4
op12
Liquid pipe temp.
T7
10
1
0
0
op13
Sc_in
T8
10
1
0
0
op14
Sc_out
T9
10
1
0
0
op15
hex_total
T10
10
1
0
0
op16
hex_hi
T11
10
1
0
0
op17
hex_low
T12
10
1
0
0
op18
Inlet pipe temp of IDU
T13
-10°
-
1
0
0
op19
main1 eev
PLS1
1940
1
9
4
0
op20
main2 eev
PLS2
32
3
2
op21
sc eev
PLS3
16
1
6
op22
oil eev
PLS4
50
5
0
op23
vi eev 1
PLS5
1350
1
3
5
0
op24
vi eev 2
PLS6
8
8
op25
IDU running capacity
IDU1
24k
2
4
op26
Total number of IDU
IDU2
10
1
0
Function