Troubleshooting Guide
- 105 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
n
Error diagnosis and countermeasure flow chart
Sensor connection to PCB
is normal?
Is the resistance of
sensor normal?*
Insert sensor connector to PCB properly
Replace sensor
Replace corresponding outdoor PCB
Yes
No
No
Is sensor resistance
value same as temperature
value of LGMV?
Yes
Yes
No
Replace corresponding sensor
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
Note: Standard values of resistance of sensors at different temperatures (5% variation)
10C = 362k : 25C= 200k : 50C= 82k : 100C= 18.5k
Check the resistance
inverter compressor
discharge temperature
sensor
Error No.
Error Type
Error Point
Main Reasons
41*
(Inverter1)
Master 411
Slave1 412
Slave2 413
Slave3 414
Compressor1 dis-
charge pipe tempera-
ture sensor error
Sensor measurement
value is abnormal
(Open/Short)
1. Defective connection of the compressor1 discharge
pipe temperature sensor
2. Defective discharge pipe compressor sensor of the
compressor1 (open/short)
3. Defective outdoor PCB
47*
(Inverter2)
Master 471
Slave1 472
Slave2 473
Slave3 474
Compressor2 dis-
charge pipe tempera-
ture sensor error
Sensor measurement
value is abnormal
(Open/Short)
1. Defective connection of the compressor1 discharge
pipe temperature sensor
2. Defective discharge pipe compressor sensor of the
compressor1 (open/short)
3. Defective outdoor PCB
Summary of Contents for ARNU05GL1G2
Page 138: ...P NO MFL67369002 April 2013 ...