4.14 Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement
or IDU addition/replacement.
4.15 Static pressure compensation mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement
or IDU addition/replacement.
Function
Master unit PCB DIP switch on : No.5
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
Vacuum mode setting method
Vacuum mode cancellation method
Push the reset button on Master unit PCB
Select the mode using
‘
ȯ
’
,
‘
ȭ
’
Button : “SVC”
Push the
‘
●
’
button
Select the Function using
‘
ȯ
’
,
‘
ȭ
’
Button : : “Se3”
Push the
‘
●
’
button
Master unit PCB DIP switch on : No.5
Select the mode using
‘
ȯ
’, ‘
ȭ
’
Button : “Func”
Push the
‘
●
’
button
Select the Function using
‘
ȯ
’, ‘
ȭ
’
Button : “Fn2”
Push the
‘
●
’
button
Select the Option using
‘
ȯ
’, ‘
ȭ
’
Button : : “op1~op3”
Push the
‘
●
’
button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
FAN Maximum RPM of each step
Static pressure compensation mode setting method
Capacity
8~12HP
14~20HP
Max. RPM
Standard
730
950
Step1
760
1020
Step2
780
1050
Step3
800
1130
Function